Coolant Distribution Unit

Our CDU decouples facilities chilled water from IT cooling to providea precisely controlled chilled water supply for immersion and direct-to-chip cooling systems.

Cooling intensive HPC and AI workloads

With a 1.5MW (1,500kW) heat capacity, the CDU-M15 efficiently supplies regulated, contaminant-free chilled water to to downstream IT cooling systems.

Whether it’s supporting direct-to-chip (DTC, also known as DLC or direct liquid cooling), immersion cooling, or rear door heat exchangers, the CDU-M15 is ideal for maintaining performance and uptime for high powered CPUs, GPUs, and ASICs.

Features and Benefits

Seamlessly integrates into existing environments

Dynamic heat management to handle load fluctuations

Intuitive touchscreen controls with BMS integration

Optional redundant power feeds

Specifications

 CDU-M15CDU-M15-600CDU-M30-1200
External Heat RejectionChilled Water or Glycol MixChilled Water or Glycol MixChilled Water or Glycol Mix
Capacity1.5 MW @ 6.5°F ATD1.5 MW @ 25°F ATD3.0 MW @ 25°F ATD
Flow Rate1.0LPM / kW1.5LPM / kW1.5LPM / kW
Secondary Flow (max)440 GPM630 GPM1320 GPM
Secondary External Pressure Drop (max)65 PSI65 PSI65 PSI
Secondary Temperature Range45 – 130°F45 – 130°F45 – 130°F
Primary Internal Pressure Drop13 PSI @ 320 GPM13 PSI @ 468 GPM13 PSI @ 936 GPM
Power Consumption (max)17.2 kW38 kW57 kW
Dimensions (L x W x H)66” x 33” x 79”100” x 37” x 79”125” x 56” x 100”
Dry Weight2,700 lbs4,000 lbs5,315 lbs

Resources

CDU-M30-1200
CDU-M15-600
CDU M15